Energy delivery efficiency index to evaluate simultaneous heating and cooling effects in large commercial buildings

T Agami Reddy, J. K. Kissock, S. Katipamula, D. E. Claridge

Research output: Contribution to journalArticle

13 Citations (Scopus)

Abstract

HVAC systems of large commercial buildings consume energy in excess of the sum total of the building loads. This excess energy use is due to the fact that a single air-handler unit in a HVAC system, having to provide conditioned air at different supply temperatures to different zones in the building, can do so only by resorting to either (a) a certain amount of mixing of cold and hot air streams as in dual-duct systems or (b) to terminal reheating in single-duct systems. This mixing of cold and hot air streams or terminal reheating result in an energy penalty which can be minimized by say, converting a constant air volume (CAV) system to a variable air volume (VAV) system, but it cannot be entirely eliminated. This paper proposes an index, called the Energy Delivery Efficiency (EDE), which characterizes this penalty and rates the energy performance of HVAC systems on an absolute scale. We develop the mathematical basis of the EDE approach for both one-zone and two-zone buildings, that allows determining the variation of the ideal EDE with outdoor temperature for a specific building. Year-long measured whole-building cooling and heating energy use data from two retrofitted buildings are finally used to illustrate differences between actual EDE plots of CAV and VAV systems, how they compare with the ideal EDE of a two-zone building, and how the approach can provide diagnostic insights into HVAC system efficiency in specific buildings.

Original languageEnglish (US)
Pages (from-to)79-87
Number of pages9
JournalJournal of Solar Energy Engineering, Transactions of the ASME
Volume116
Issue number2
StatePublished - May 1994
Externally publishedYes

Fingerprint

Cooling
Heating
Air
Ducts
Temperature
HVAC

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Fuel Technology
  • Renewable Energy, Sustainability and the Environment
  • Mechanical Engineering

Cite this

Energy delivery efficiency index to evaluate simultaneous heating and cooling effects in large commercial buildings. / Reddy, T Agami; Kissock, J. K.; Katipamula, S.; Claridge, D. E.

In: Journal of Solar Energy Engineering, Transactions of the ASME, Vol. 116, No. 2, 05.1994, p. 79-87.

Research output: Contribution to journalArticle

@article{5fc977d343e8462d9bbede7b667a7b0a,
title = "Energy delivery efficiency index to evaluate simultaneous heating and cooling effects in large commercial buildings",
abstract = "HVAC systems of large commercial buildings consume energy in excess of the sum total of the building loads. This excess energy use is due to the fact that a single air-handler unit in a HVAC system, having to provide conditioned air at different supply temperatures to different zones in the building, can do so only by resorting to either (a) a certain amount of mixing of cold and hot air streams as in dual-duct systems or (b) to terminal reheating in single-duct systems. This mixing of cold and hot air streams or terminal reheating result in an energy penalty which can be minimized by say, converting a constant air volume (CAV) system to a variable air volume (VAV) system, but it cannot be entirely eliminated. This paper proposes an index, called the Energy Delivery Efficiency (EDE), which characterizes this penalty and rates the energy performance of HVAC systems on an absolute scale. We develop the mathematical basis of the EDE approach for both one-zone and two-zone buildings, that allows determining the variation of the ideal EDE with outdoor temperature for a specific building. Year-long measured whole-building cooling and heating energy use data from two retrofitted buildings are finally used to illustrate differences between actual EDE plots of CAV and VAV systems, how they compare with the ideal EDE of a two-zone building, and how the approach can provide diagnostic insights into HVAC system efficiency in specific buildings.",
author = "Reddy, {T Agami} and Kissock, {J. K.} and S. Katipamula and Claridge, {D. E.}",
year = "1994",
month = "5",
language = "English (US)",
volume = "116",
pages = "79--87",
journal = "Journal of Solar Energy Engineering, Transactions of the ASME",
issn = "0199-6231",
publisher = "American Society of Mechanical Engineers(ASME)",
number = "2",

}

TY - JOUR

T1 - Energy delivery efficiency index to evaluate simultaneous heating and cooling effects in large commercial buildings

AU - Reddy, T Agami

AU - Kissock, J. K.

AU - Katipamula, S.

AU - Claridge, D. E.

PY - 1994/5

Y1 - 1994/5

N2 - HVAC systems of large commercial buildings consume energy in excess of the sum total of the building loads. This excess energy use is due to the fact that a single air-handler unit in a HVAC system, having to provide conditioned air at different supply temperatures to different zones in the building, can do so only by resorting to either (a) a certain amount of mixing of cold and hot air streams as in dual-duct systems or (b) to terminal reheating in single-duct systems. This mixing of cold and hot air streams or terminal reheating result in an energy penalty which can be minimized by say, converting a constant air volume (CAV) system to a variable air volume (VAV) system, but it cannot be entirely eliminated. This paper proposes an index, called the Energy Delivery Efficiency (EDE), which characterizes this penalty and rates the energy performance of HVAC systems on an absolute scale. We develop the mathematical basis of the EDE approach for both one-zone and two-zone buildings, that allows determining the variation of the ideal EDE with outdoor temperature for a specific building. Year-long measured whole-building cooling and heating energy use data from two retrofitted buildings are finally used to illustrate differences between actual EDE plots of CAV and VAV systems, how they compare with the ideal EDE of a two-zone building, and how the approach can provide diagnostic insights into HVAC system efficiency in specific buildings.

AB - HVAC systems of large commercial buildings consume energy in excess of the sum total of the building loads. This excess energy use is due to the fact that a single air-handler unit in a HVAC system, having to provide conditioned air at different supply temperatures to different zones in the building, can do so only by resorting to either (a) a certain amount of mixing of cold and hot air streams as in dual-duct systems or (b) to terminal reheating in single-duct systems. This mixing of cold and hot air streams or terminal reheating result in an energy penalty which can be minimized by say, converting a constant air volume (CAV) system to a variable air volume (VAV) system, but it cannot be entirely eliminated. This paper proposes an index, called the Energy Delivery Efficiency (EDE), which characterizes this penalty and rates the energy performance of HVAC systems on an absolute scale. We develop the mathematical basis of the EDE approach for both one-zone and two-zone buildings, that allows determining the variation of the ideal EDE with outdoor temperature for a specific building. Year-long measured whole-building cooling and heating energy use data from two retrofitted buildings are finally used to illustrate differences between actual EDE plots of CAV and VAV systems, how they compare with the ideal EDE of a two-zone building, and how the approach can provide diagnostic insights into HVAC system efficiency in specific buildings.

UR - http://www.scopus.com/inward/record.url?scp=0028436651&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=0028436651&partnerID=8YFLogxK

M3 - Article

AN - SCOPUS:0028436651

VL - 116

SP - 79

EP - 87

JO - Journal of Solar Energy Engineering, Transactions of the ASME

JF - Journal of Solar Energy Engineering, Transactions of the ASME

SN - 0199-6231

IS - 2

ER -