Abstract
This paper deals with the development of a procedure to relate the transient energy margin of a multi-machine power system to the apparent impedance of a line protected by an out-of-step relay. In this procedure, only the multi-machine system parameters are used, and the conventional intermediate step of forming a two-machine equivalent is eliminated. A technique for generating the swing impedance locus is also described. The method is tested for a loss of generation disturbance on a 23-generator equivalent of the Florida Power & Light Co. network. The results obtained are compared with time simulation results.
Original language | English (US) |
---|---|
Pages (from-to) | 455-462 |
Number of pages | 8 |
Journal | IEEE Transactions on Power Systems |
Volume | 3 |
Issue number | 2 |
DOIs | |
State | Published - May 1988 |
Externally published | Yes |
ASJC Scopus subject areas
- Energy Engineering and Power Technology
- Electrical and Electronic Engineering